1. A healthy trap and vent
At the fixture: nothing. The toilet flushes and the basin stays quiet. In the pipe: the water falling through the shared drain drags air along with it, and that air has to be replaced. With the vent open, it comes down the vent from the roof. Pulling 5 litres a second through 20 feet of 1½-inch pipe costs about a quarter of an inch of water, so the pressure at the trap dips by that much and recovers.
Why the trap survives: a trap is a U-tube manometer. A suction of a inches of water lifts the outlet side and lowers the inlet side until the two levels differ by a [4]. A quarter of an inch spills a little water over the weir and leaves the seal at about 1.9 of its 2 inches. That is the vent doing its job: designers size it to hold the pressure within ±1 inch [3].
2. No vent: the basin siphons its own trap
At the fixture: the basin drains, then gives a loud gulp at the end. In the pipe: the meter swings to the seal’s limit and stays pinned there until the water has gone. The toilet’s bowl, on the same branch, feels the same pull: its water drops too.
Why: with no vent near the trap, the water falling through the drain below it acts as the long leg of a siphon. It needs air to follow it, and the only air available is on the far side of the trap. Suction builds until it equals the seal depth, the inlet side reaches the dip, and room air bubbles through: the gurgle. This is self-siphonage, the fixture emptying its own trap, and its severity depends on the drain’s length, slope and diameter, the trap and the rate of discharge [1].
Also: codes deal with it by limiting how far, and how far down, a trap arm may run before it meets its vent; the Uniform Plumbing Code, for example, does not let the vent opening sit below the trap’s weir [5]. Requirements differ between the codes in use (IPC, UPC and local amendments), so what is allowed where you live is a question for the local code and a licensed plumber.
3. Blocked vent: the sink gurgles when the toilet flushes
At the fixture: flush the toilet and the basin (or a tub, or the toilet’s own bowl) gurgles. In the pipe: the same flush as step 1, but the vent is 88 percent blocked, and the suction runs straight past the band to the seal’s limit.
Why: the flush needs the same air as before. Through a nearly closed vent it can get only part of it, so the pressure in the branch falls until the next path opens, and the next path is the basin’s trap. Water spills over the weir, the inlet side drops to the dip, and room air is pulled through in gulps. In this idealised model the seal is left half full after one flush. Losing seal to another fixture’s discharge is what the NBS researchers called siphonage, to tell it apart from self-siphonage [1].
Also: a vent can be choked by leaves, a nest, ice or debris at the roof, or be too small or too long for the flow it serves. Drag the vent handle in the figure: the trap holds until the vent is roughly three-quarters blocked, then fails quickly. A drain that is slow without any gurgling points first to a partial blockage in the trap or the drain line, which no vent can fix [1].
4. S-trap: the shape that siphons itself
At the fixture: the basin drains fine, sometimes with a slurp, but there is a faint sewer smell near it. In the pipe: the outlet of the trap turns straight down, and the vertical leg runs full of water as the basin empties.
Why: an S-trap carries its own siphon leg. Our drawing gives it 18 inches of full-bore drop under a 2-inch seal, and nothing to let air in at the top of that leg. Every time the basin drains, the seal is pulled to the dip and air breaks through. The idealised model leaves half the water behind; real S-traps often lose more, because the water keeps moving after the flow ends and bubbles drag water out with them [1]. A half-empty seal then holds only half the back-pressure it did, so the next push of air down the drain lets drain air through. The Uniform Plumbing Code prohibits S-traps outright [5].
5. Dry trap: the smell from a drain nobody uses
At the fixture: a sewer smell from a guest-bathroom shower, a basement floor drain or a utility sink that has not run for weeks. In the pipe: no event at all. The meter reads zero; the trap is empty.
Why: water evaporates from both surfaces of the trap. With no water there is no seal, and drain air drifts into the room with no pressure difference needed. A dry trap is the most common cause of sewer odour indoors [6], and a university safety procedure traces localised sulfur smells to dry sink traps and unused floor drains, prevented by running water into them at least once a week [7]. How fast a trap dries depends on heat, dry air and air moving over it: measurements from the 1880s found anywhere from about one inch a week to more than two [8]. The figure assumes a slower quarter-inch a week, which empties a 2-inch trap in 8 weeks.
Also: codes require trap seal primers, devices that top up the water, on floor drains that see little use [5]. A smell that comes back right after the trap is refilled points elsewhere: a cracked or loose drain or vent pipe, a failed wax ring under a toilet, or a trap whose seal is being pulled out (steps 2 to 4).
6. Air admittance valve: a vent that only breathes in
At the fixture: nothing, as in step 1. In the pipe: when the flush pulls, the valve’s seal lifts and room air flows in; the suction stops at a little more than half an inch. When the flow stops, the valve drops shut.
Why: an air admittance valve (AAV) is a one-way vent. It opens under a small suction (one maker lists −70 Pa, about a quarter of an inch of water) and is tight at zero or positive pressure, so sewer air cannot come out of it [9]. That is also its limit: it cannot let air out. Pressure pushing up the drain must still escape through an open vent, which is why the International Plumbing Code still requires at least one vent pipe to the outdoors on every building drain, and sets limits on where AAVs may be used [10].
Also: AAVs must stay accessible for replacement and be installed the way the code and the maker require [10]. Whether one is acceptable in your house is a local code question.
7. Wind over the roof: gurgles on a gusty day
At the fixture: a gurgle or a faint whiff on windy days, with nothing draining. In the pipe: the meter rocks below zero with each gust.
Why: air moving fast across the open top of the vent is at lower pressure than still air (Bernoulli) [4], and the vent connects that pressure straight to the trap. At 55 mph, with an illustrative pressure coefficient of −0.5, gusts pull about three-quarters of an inch of water: inside the design band, but each gust spills a little and rocks the seal. Real traps lose more than this quasi-static model shows, because the water sloshes in time with the gusts.
Also: a vent terminal close to a roof edge, a wall or a ridge sits where the wind speeds up most. Changing a vent terminal is roof work and a code matter: a job for a licensed plumber.