Superheat and subcooling calculator
Gauge pressure and line temperature in; saturation temperature, superheat and subcooling out, for R-410A or R-32.
How it is calculated
A gauge reads pressure above the atmosphere. The property tables use absolute pressure, so the calculator first adds a standard atmosphere, 14.696 psi or 101.325 kPa [1]. It then looks up the temperature at which the refrigerant boils or condenses at that pressure: the saturation temperature, the number on a pressure–temperature chart.
Superheat uses the dew point, the temperature at which the last liquid boils off; subcooling uses the bubble point, the temperature at which the first bubble forms. For R-32, a single substance, the two are the same. For R-410A, a blend, they differ by about 0.1 K, or 0.2°F [2], so either is fine in practice, but the calculator uses the right one for each side.
The saturation temperatures come from Lemmon’s 2003 equation of state for R-410A, with its dew- and bubble-pressure equations, and from Tillner-Roth and Yokozeki’s 1997 equation for R-32 [2][3], evaluated with CoolProp [4] and tabulated every 1 K. The table reproduces the equations’ saturation pressures to better than 0.001%, which is far below any gauge’s error.
Worked example
An R-410A system reads 118 psig on the suction line, and a clamp on the suction line reads 50°F. 118 psig is 132.7 psia. At that pressure R-410A’s dew point is 39.8°F, so the superheat is 50 − 39.8 = 10.2°F. On the liquid line, 356.5 psig is the pressure at which R-410A condenses at 108°F; a training example from HVAC School uses exactly this pair for a 15 SEER system on an 88°F day [5]. With the liquid line at 98°F, the subcooling is 108 − 98 = 10°F.
The same readings on an R-32 system give a different answer: at 118 psig R-32 boils at 38.7°F, so the same 50°F line means 11.3°F of superheat. Selecting the wrong refrigerant is one of the easiest ways to get a misleading number.
What the result does and does not tell you
Superheat and subcooling describe the state of the refrigerant at the point where they are measured. Whether a value is right depends on the system. Systems with a thermostatic expansion valve are usually checked by subcooling against the maker’s figure; Carrier’s heat pump labels, for example, give the required subcooling on the unit’s rating plate, within ±3°F [6]. Systems with a fixed orifice are usually checked by superheat, against a target that depends on the indoor wet-bulb and outdoor temperatures and can run from 5 to 40°F [7]. A typical TXV system shows 8 to 12°F of subcooling [7], but the equipment maker’s data decides. The essay explains what high and low combinations commonly point to; those are common causes, not a diagnosis.
Assumptions and valid range
- Refrigerants: R-410A and R-32 only. R-454B, R-22 and others are not supported; their pressures and temperatures differ, and entering their readings here gives wrong answers.
- Pressures are gauge pressures, converted with the sea-level standard atmosphere. At altitude the air pressure is lower, so the same gauge reading means a slightly lower absolute pressure than the calculator assumes; the error is small at the pressures in these systems, larger on the suction side than on the liquid side.
- Accepted inputs: pressures from −14.6 to 800 psig (−100 to 5,515 kPa(g)) and temperatures from −60 to 200°F (−51 to 93°C). Saturation lookups cover about 3 to 630 psig for R-410A and 3 to 720 psig for R-32 (−54°F up to about 152°F or 161°F); outside that the calculator says so.
- A reading on the wrong side of saturation (a suction line colder than the boiling point, a liquid line warmer than the condensing point) is reported in words rather than as a negative number, because it means liquid or vapour where there should be none, or a measurement problem.
- This is a measurement aid for understanding, not a charging procedure or a diagnosis. Equipment makers’ instructions decide targets.
Gauges go on only in certified hands. Connecting gauges to a refrigerant circuit, and adding or removing refrigerant, is work for a technician certified under Section 608 of the Clean Air Act; refrigerant may not be knowingly released, and only certified technicians may buy it [8]. If you are a homeowner, use these numbers to understand what your technician tells you.
Sources
- (2008). Guide for the Use of the International System of Units (SI), NIST SP 811, Appendix B.8 Factors for units listed alphabetically. National Institute of Standards and Technology. standard Standard atmosphere = 1.01325 × 10⁵ Pa; 1 psi = 6.894757 × 10³ Pa (so 1 atm = 14.696 psi); T/K = (t/°F + 459.67)/1.8; 1 Btu_IT/lb = 2326 J/kg.
- (2003). Pseudo-Pure Fluid Equations of State for the Refrigerant Blends R-410A, R-404A, R-507A, and R-407C. International Journal of Thermophysics 24(4): 991–1006 (copy hosted by NIST). journal article R-410A = 50% R-32 / 50% R-125 by mass; Helmholtz-energy equation fitted to the full mixture model (densities within 0.1% except near the critical point; heat capacities 0.1% average, 0.5% max); dew and bubble pressures from ancillary Eq. 13 (Table VI), within 0.02–0.05% of the mixture model; valid 200–450 K; Table V check values (300 K: bubble 1.7404 MPa, dew 1.7351 MPa); dew and bubble curves of R-410A nearly coincident.
- (1997). An International Standard Equation of State for Difluoromethane (R-32) for Temperatures from the Triple Point at 136.34 K to 435 K and Pressures up to 70 MPa. Journal of Physical and Chemical Reference Data 26(6): 1273–1328. doi:10.1063/1.556002. journal article Read via the NIST Chemistry WebBook fluid page for R-32, which uses this equation and states its estimated uncertainties: 0.05% for density, 0.02% for vapor pressure, 0.5–1% for liquid heat capacity and speed of sound.
- (2014). Pure and Pseudo-pure Fluid Thermophysical Property Evaluation and the Open-Source Thermophysical Property Library CoolProp. Industrial & Engineering Chemistry Research 53(6): 2498–2508. doi:10.1021/ie4033999. software CoolProp (MIT licence), version 8.0.0, implements the Lemmon (2003) R-410A and Tillner-Roth & Yokozeki (1997) R-32 equations used to build this site's property tables.
- (2021). “The Pressures Look Good.” How Do You Know?. HVAC School. trade training Evaporator design temperature difference (DTD) about 35 °F ± 3 below return air; condensing temperature over ambient (CTOA) 30 °F (6–9 SEER), 25 °F (10–12), 20 °F (13–16), 15 °F (17+); worked example for R-410A: 74 °F return, 88 °F outdoor → 39 °F evaporating (116.1 psig) and 108 °F condensing (356.5 psig).
- (2015). 25HBB5 Base Series Heat Pump with Puron Refrigerant: wiring diagrams and charging label. Carrier Corporation. manufacturer manual Required subcooling is given on the unit rating plate, with a ±3 °F tolerance; reversing valve solenoid and defrost control in the ladder diagram; relieve pressure and recover all refrigerant before system repair or final disposal.
- (2012). A/C-Heat Pump System Troubleshooting Guide for the Testo 550. TruTech Tools, Akron, OH. trade training Tables of suction pressure, liquid pressure, superheat and subcooling direction for common faults on fixed-orifice and TXV systems (overcharge, undercharge, liquid restriction, low evaporator airflow, dirty condenser, low ambient, inefficient compressor, non-condensables, TXV bulb faults); typical TXV subcooling 8–12 °F, evaporator superheat 6–12 °F; fixed-orifice target superheat 5–40 °F depending on indoor wet bulb and outdoor dry bulb; DTD 35 °F, condenser +20 to +30 °F; check airflow first; measure both superheat and subcooling.
- (2020). EPA’s Refrigerant Management Requirements: What Technicians Need to Know (Section 608 fact sheet). U.S. EPA. government guidance Section 608 prohibits knowingly releasing refrigerant during maintenance, service, repair or disposal; requirements cover HCFCs and non-exempt substitutes such as HFCs and HFOs; only certified technicians can use non-exempt refrigerants to service AC and refrigeration equipment; refrigerant sales restricted to certified technicians; technicians must pass an approved certification exam.